Formulas: Concrete Floor Slabs on Steel Deck

PDF page 332 · AISC 360-22

Equation A-4-33

For composite concrete floor slabs on trapezoidal steel decking wherein the upper width of the deck rib is equal to or greater than its bottom rib width, the fire-resistance rating, based on the thermal insulation criterion for the unexposed surface temperature, is permitted to be calculated using the following equation:

R=a0+a1h1+a2h2+a3l2+a4l3+a5m+a6h12+a7h1h2+a8h1l2+a9h1l3+a10h1m+a11h2l2+a12h2l3+a13h2m+a14l2l3+a15l2m+a16l3m\begin{aligned} R & =a_{0}+a_{1} h_{1}+a_{2} h_{2}+a_{3} l_{2}+a_{4} l_{3}+a_{5} m+a_{6} h_{1}^{2} \\ & +a_{7} h_{1} h_{2}+a_{8} h_{1} l_{2}+a_{9} h_{1} l_{3}+a_{10} h_{1} m+a_{11} h_{2} l_{2} \\ & +a_{12} h_{2} l_{3}+a_{13} h_{2} m+a_{14} l_{2} l_{3}+a_{15} l_{2} m+a_{16} l_{3} m \end{aligned}

where

  • R=R= fire-resistance rating, min
  • h1=h_{1}= concrete slab thickness above steel deck, in. (mm)
  • h2=h_{2}= depth of steel deck, in. (mm)
  • l1=l_{1}= largest upper width of deck rib, in. (mm)
  • l2=l_{2}= bottom width of deck rib, in. (mm)
  • l3=l_{3}= width of deck upper flange, in (mm)
  • m=m= moisture content of the concrete slab, %. Range of applicability is between 0%0 \% (0.0) and 10%10 \% (0.1).

Formula 2

User Note: If moisture content values are not available, m=4%m=4 \% can be used for normal weight concrete, and m=5%m=5 \% can be used for lightweight concrete, consistent with Annex D of Eurocode 4.

m=4%m=4 \%

Formula 3

m=5%m=5 \%

Formula 4

Dry conditions ( m=0%m=0 \% ) will yield the most conservative fire-resistance rating.

m=0%m=0 \%